1 - 23
1
Mini VRF SYSTEM
Control Functions
16. Detailed Settings in EEPROM of Outdoor Unit
Never use the DN code unlisted in the following table. (P) : Factory preset mode
DN Item Setting No.
04 Operation for using snowfall sensor
0=No sensor & control (P)
2=No sensor & no control
1=Sensor & control
3=Sensor & no control
05 Outdoor fan silent mode
0=Invalid (P)
2=Never use
1=Silent mode
3=Never use
(For detail, refer to 7-5)
0C Indoor unit drain pump forced operation
0=Invalid
1=stop for 2 hours and drive for 20 minutes constantly
2=stop for 20 minutes and drive for 20 minutes constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
8-11=delay drive when stopped
12-15=Delay drive when thermostat OFF & stopped
(For detail, refer to 9-4)
0D
Measures against smell when indoor unit cooling
thermostat OFF
0=Invalid (P)
1=Measures against smell
1A Demand 1 current (%)
0=0% ,,,,,
45=45% ,,,,,
160=160%
40=40% ,,,,,
100=100% (P) ,,,,,
-1=No control
(For detail, refer to 15-1)
1B Demand 2 current (%)
0=0% ,,,,,
70=70% (P) ,,,,,
160=160%
40=40% ,,,,,
100=100% ,,,,,
-1=No control
(For detail, refer to 15-1)
1E Demand remote controller display
0=No demand display
1=When demand ON, “ready to start” display (P)
2=When forced thermostat OFF with demand ON,
“ready to start” display
(For detail, refer to 15-2)
23 E06 ignore function
-1=Invalid (P)
1=1 ,,,,,
14 - 52=Never use
0=0
13=13
2A Dew condensation prevention control of indoor unit
0=Invalid (P)
2=40 minutes
4=60 minutes
1=30 minutes
3=50 minutes
2B DP operation time for slime measures
20=20 minutes
40=40 minutes
60=60 minutes
30=30 minutes (P)
50=50 minutes
(For detail, refer to 9-4)
2C Indoor unit fan stop temperature shift
-30=-30°C ,,,,,
50=+50°C
0=+0°C (P) ,,,,,
(For detail, refer to 9-3-2)
35
Condensation temperature adjustment
Lower temperature of B area (Tc_B) for heating mode
-7=-7°C
0=0°C (P) ,,,,,
-6=-6°C ,,,,,
7=7°C
(For detail, refer to 2-3-3)
36
Condensation temperature adjustment
Upper temperature of B area (Tc_B) for heating mode
-7=-7°C
0=0°C (P) ,,,,,
-6=-6°C ,,,,,
7=7°C
(For detail, refer to 2-3-3)
3E PSccutgt delay-start setting
0=8 seconds delay-start (P)
1=(system address x1x8) second delay-start
2=(system address x2x8) second delay-start
3=(system address x3x8) second delay-start
(For detail, refer to 14-2)
SM830195-04_Mini VRF SYS.indb 23 15/03/10 17:47:37

Table of Contents

Other manuals for Panasonic EAIRC-MJ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic EAIRC-MJ Series and is the answer not in the manual?

Panasonic EAIRC-MJ Series Specifications

General IconGeneral
BrandPanasonic
ModelEAIRC-MJ Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals