Basic Instructions
2 − 120
Keyword setting
1) Communication format (Shared by the Tool, COM. 1 and COM. 2 ports)
Character bit
B7: 7bits B8: 8bits
Port used
TOOL: Tool port
COM1: COM. 1 port
COM2: COM. 2 port
Parity
PN: None PO: Odd PE: Even
Stop bit
S1: 1 S2: 2
SYS1, M TOOL,B7 PN S1
2) Baud rate (Shared by the Tool, COM. 1 and COM. 2 ports)
Port used
TOOL: Tool port
COM1: COM. 1 port
COM2: COM. 2 port
Baud rate
300: 300 bps 600: 600 bps
1200:1200 bps 2400: 2,400 bps
4800: 4,800 bps 9600: 9,600 bps
19200: 19,200 bps 38400: 38,400 bps
57600: 57,600 bps 115200: 115,200 bps
SYS1, M TOOL,19200
The baud rates of 300, 600 or 1200 bps can be specified only with the FP0R, FP−X ver 2.0 or later and FPΣ ver3.10 or later.
Also, those baud rates cannot be specified by the system register.
3) Unit No. (Shared by the Tool, COM. 1 and COM. 2 ports)
Port used
TOOL: Tool port
COM1: COM. 1 port
COM2: COM. 2 port
Unit No.
No1 to No99: No. 1 to No. 99
SYS1, M TOOL,No1
For FP0R, the indirect settings of unit number is available.
Port used
TOOL: Tool port
COM1: COM. port
DT number that Unit No. is stored.
SYS1, M COM1, D000D
D000D = DT0
D9999 = DT9999
Always specify with a number of D+4 digits.
FPΣ/FP−X/FP0R