Basic Instructions
2 121
4) Header and Terminator (Shared by the TOOL, the COM. 1 and COM. 2 ports)
Port used
TOOL: Tool port (FPΣ 32k/FPX/FP0R)
COM1: COM. 1 port
COM2: COM. 2 port
Header
STX: STX
NOSTX: STX not exist
Terminator
ETX: ETX
CR: CR
CRLF: CR + LF
NOTERM: None
SYS1, M COM1,STX
5) RS (Request to Send) control (COM. 1 port only)
Port used
COM1: COM. 1 port
RS control for the 1channel RS232C type
communication cassette
RTS1: Disables communication
(Sets the RS terminal to “on”)
RTS0: Enables communication
(Sets the RS terminal to “off”)
SYS1, M COM1,RTS1
* Not available for FP0R.
Precautions during programming
Executing this instruction does not rewrite the contents of the
system ROM in the control unit. As a result, turning the power
supply off and then on again rewrites the contents of the system
registers specified by the tool software.
We recommend using differential execution with this instruction.
Because the system register settings are changed, a verification
error may occur in some cases if verification is carried out with the
tools.
For No. 1 and No. 2 keywords, input 12 letters after “M” aligning to the
right. Separate No.1 and No.2 keywords with a comma ”,” and do not
use spaces. An operation error will occur.
[Example] If inputting (SYS1, M COM1, WAIT2)
Input => M
COM1,WAIT2
Input a space after “M” to be 12 letter aligning to the right.
For FP0R, specify COM1 for COM port.
FPΣ/FPX/FP0R