Relays, Memory Areas and Constants
1-38
Even if specifying for the unit without batteries, the data will be indefinite.
Value of system register 6
(initial number of hold type)
Non-hold
type
Hold type
Default settings for hold types and nonhold types
Type Nonhold type Hold type
FP2SH/FP10SH 0 to 2999 (3000 points) 3000 to 3071 (72 points)
FP2 0 to 999 (1000 points) 1000 to 1023 (24 points)
FPΣ,FPX, FP0R 0 to 1007 (1008 points) 1008 to 1023 (16 points)
FPe
0 to 139 (140 points) 140 to 143 (4 points)
SV: nonhold
*1
SV: hold
FP0 T32C 0 to 99 (100 points) 100 to 143 (44 points)
Note
For FP0R, FPΣ,FPX and FPe, in case of not using backup
battery, please keep the default value. Otherwise we cannot
guarantee the function of hold/nonhold value.
*1 Use the following methods for holding the SV data:
Set the transfer instruction for the data register (DT) to
hold the data. Then, perform the setting so that the data
can be transferred from DT to SV after the RUN mode
starts.
Use the FPe model with a battery.
For the FP2/FP2SH/FP10SH, contacts of timers and counters specified as hold types,
as well as setting value areas and elapsed value areas, are cleared to 0 when the
Initialize/Test switch is set to the upper side (the Initialize side).
Note
With the FP2SH/FP10SH, system register 4 can be set in such a
way that the counter contact is not cleared even if the
Initialize/Test switch is set to the upper side.