High−level Instructions
3 − 607
Converts 32−bit data (H00000123 and H0089ABCD) to hexadecimal ASCII codes (Normal direction)
DT10、11 = H 123
DT12、13 = H 89ABCD
”230100CDAB89”
When No. of converted data is ”2”, Starting position for storing is ”0”, Size of the area for storing is ”6”.
F251 ATOB, D−16, DT 10, DT20, DT100
R0
F250 BTOA, 32+H, DT10 , H 206 , DT 100
M
(DF)
For the reverse direction (when ”32+H” is ”32−H”)
Flag conditions
ΣError flag (R9007): Turns on and stays on when
Σ Error flag (R9008): Turns on for an instant when
− There is an error in the control string specified by S1.
− The direction of converted data is changed to the normal direction when the
conversion format specified by S1 is in decimal.
− The size of the area for storing ASCII codes specified by N exceeds the
rated value when the conversion format specified by S1 is in hexadecimal.
(Rated value for 16−bit data: 4) (Rated value for 32−bit data: 8)
− The No. of the converted data specified by N is 0.
− The converted result exceeds the area for storing ASCII codes specified by N.
− The converted result exceeds the area.
− The area specified using the index modifier exceeds the limit.
FPΣ/FP−X/FP0R