High−level Instructions
3 − 665
Outline This instruction carries out zone control for 16-bit data.
For the FP0R/FPΣ/FP−X, the P type high−level instruction “P289
(PZONE)” is not available.
Program example
Ladder
Diagram
Boolean
Ladder Diagram
Address Instruction
S1
Trigger
S3S2 D
F289 ZONE, DT10, DT20, DT30, DT40
10
R0
10
11
ST R 0
F289 (ZONE)
DT 10
DT 20
DT 30
DT 40
S1 Area where negative bias value is stored or negative bias value data
S2 Area where positive bias value is stored or positive bias value data
S3 Area where input value is stored or input value data
D Area where output value is stored
Operands
O
p
erand
Relay Timer/Counter Register
Index
register
Constant
Index
modifier
Integer
device
Operand
WX WY WR WL SV EV DT LD FL I K H f
modifier device
S1 A A A A A A A A A A A A N/A A N/A
S2 A A A A A A A A A A A A N/A A N/A
S3 A A A A A A A A A A A A N/A A N/A
D N/A A A A A A A A A A N/A N/A N/A A N/A
Explanation of example
When the DT10 is “K−100” and DT20 is “K100”.
Value of DT30
K−300
K−200
K−100
K0
K100
K200
K300
Value of DT40
K−400
K−300
K−200
K0
K200
→
→
→
→
→
→
→
K300
K400
F289
P289
(PZONE)
(ZONE)
16-bit data zone control
A
:
A
vailable
N/A: Not Available