Reads the on and off status of contacts. 
・Specifies only one point. 
・Specifies multiple contacts. 
・
Write contact area 
WC 
(WCS) 
(WCP) 
(WCC) 
Turns contacts on or off. 
・Specifies only one point. 
・Specifies multiple contacts. 
・Specifies a range in word units. 
Read data area  RD  Reads the contents of a data area. 
Write data area  WD  Writes data to a data area. 
Read timer/counter set 
value area 
RS  Reads the timer/counter setting value. 
Write timer/counter set 
value area 
WS  Writes the timer/counter setting value. 
Read timer/counter 
elapsed value area 
RK  Reads the timer/counter elapsed value. 
Write timer/counter 
elapsed value area 
WK  Writes the timer/counter elapsed value. 
Register or Reset 
contacts monitored 
MC  Registers the contact to be monitored. 
Register or Reset data 
monitored 
MD  Registers the data to be monitored. 
Monitoring start  MG  Monitors a registered contact or data using MD and MC. 
Preset contact area (fill 
command) 
SC 
Embeds the area of a specified range in a 16-point on and off 
pattern. 
Preset data area (fill 
command) 
SD  
Writes the same contents to the data area of a specified 
range. 
Read system register  RR  Reads the contents of a system register. 
Write system register  WR  Specifies the contents of a system register. 
Read the status of PLC  RT 
Reads the specifications of the programmable controller and 
Remote control  RM 
Switches the operation mode of the programmable controller. 
(RUN mode <=> PROG. mode) 
Abort  AB  Aborts communication.