Heating in operation according to Remote Control setting.
Time Delay Safety Control
- When the compressor is stopped by Remote Control, it restarts
after 3 minutes when the Remote Control is turned ON.
- When the setting temperature is reached during heating operation,
the compressor stops and it will not start for 4 minutes. /
30 minutes Time Save Control
- The compressor will start automatically if it has stopped for 30
minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
Overload Protection Control
- If the temperature of the indoor heat exchanger rises to 51°C,
Outdoor Fan stops.
The Outdoor Fan restarts when the indoor heat exchanger
temperature falls to 49°C.
- If the indoor heat exchanger becomes 65°C or more, the
compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting).
Compressor Reverse Rotation Protection Control
- If the compressor is operating continuously for 5 minutes or longer
and temperature difference between intake air and indoor heat
exchanger is C or less for 2 minutes, compressor will stop and
restart automatically.
25