EVALUATION OF THE PERFORMANCE
- Operate the unit at cooling operation mode for fifteen minutes or
more.
- Measure the temperature of the intake and discharge air.
- Ensure the difference between the intake temperature and the
discharge is more than C.
NOTE
These equipment shall be connected to a
suitable mains network with a main impedance
less than the following:
CS-A75KR / CU-A75KR: 0.33
CS-A95KR / CU-A95KR: 0.23
CS-A125KR / CU-A125KR: 0.2
CHECK ITEMS