Hot Start Control
When Heating operation starts, Indoor Fan will not start until the
indoor heat exchanger reaches 30°C as diagram shown.
Hot Start is completed when indoor heat exchanger rises to 39°C.
Anti Cold Draft Control
- This operation is to prevent the Cold Draft during Heating mode
operation.
- The operation will start when compressor OFF (Thermo OFF)
during Heating operation.
- For the first 30 sec from compressor OFF (Thermo OFF), Indoor fan
speed will operate accordingly to the Indoor heat exchanger
temperature as shown below:
27