8.4. Automatic Mode Operation
1. When the Automatic Mode Operation is selected, the indoor fan
operates at Lo fan speed for 25 seconds to sense intake air
temperature and determine the 1st operation mode.
2. Operation mode will be determine again after 1 hour of operation,
if the room temperature reaches to set temperature and
compressor off time is over 7 minutes 30 seconds continuously.
The present operation mode will be continued, if the room temperature does not reach to set
temperature (Compressor keeps running) eventhough after 1 hour from automatic operation
started.