EasyManua.ls Logo

Panasonic S-200PE1E8 - Page 58

Panasonic S-200PE1E8
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-52
1
Restriction on the number of passes of the heat exchanger hairpin
Minimum number of passes
= Number of steps × Distance between tube sheets × Number of rows × 1.5 ×10
-4
<For example>
Number of steps 12
Distance between tube sheets 1000 [mm]:
:
:Number of rows 3
Minimum number of passes = 12 × 1000 × 3 × 1.5 × 10
-4
= 5.4 < 6 passes
SM830194-02BigPAC-i.indb52SM830194-02BigPAC-i.indb52 2012/09/0311:23:432012/09/0311:23:43