2
2-11
2-14. Table of Self-Diagnostic Functions and Corrections
Wired remote
controller
display
(Field supply)
Indoor unit
receiver lamp
Cause
Correction
1:1 connection (Single type)
Group connection
(Simultaneous multi
system)
Nothing is
displayed
Nothing is
displayed
• Indoor operation switch is OFF.
• Indoor unit power is not ON.
• Same at left. • Set the indoor operation switch ON.
• Turn ON the indoor unit power.
E01 displayed
Operating lamp
is blinking.
• Automatic address setting has not
been completed.
• Inter-unit control wiring is cut or is
not connected correctly.
• Same at left. • Check the inter-unit control wiring.
• Perform automatic address setting
(See 2-15).
E14
——————
• Remote controller
communication wiring is
cut or is not connected
correctly.
• Check the remote controller communication
wiring.
• Perform automatic address setting again.
E04 displayed
displayed
Standby lamp is
blinking.
• Indoor-outdoor inter-unit wiring is
not connected correctly.
• Same at left. • Connect the wiring correctly.
E06
——————
• Inter-unit control
wiring is cut or is not
connected correctly.
• Refer to 2-15 System Control, and make
the correct settings.
E15 displayed
displayed
• Indoor unit capacity is too low. • Same at left. • Check that the total capacities of the indoor
and outdoor units are appropriate.
E16 displayed
• Indoor unit capacity is too high. • Same at left. • Reverse 2 phases of the outdoor unit
3-phase power and connect them correctly.
P05 displayed
Operation lamp
and Standby
lamp are blinking
alternately.
• Reversed phase in the outdoor unit
single-phase or open phase in the
outdoor unit 3-phase power.
• Same at left. • Connect the units correctly.
L02 displayed
Both the
Operation lamp
and Standby
lamp are blinking
together.
• Indoor-outdoor unit type mismatch. • Same at left. • Connect the units correctly.
L13 displayed
• Indoor-outdoor units are not setting
correctly.
• Same at left. • Connect the units correctly.
L04
——————
• Outdoor unit address is
duplicated.
• Connect the units correctly.
L07 ——————
• Remote controller
communication wiring is
connected to the indoor
unit, however, it is set
for individual operation.
• Perform automatic address setting
(See 2-15).
P15 displayed
displayed
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
• Check the refrigerant cycle (for gas • Same at left • No gas
leaks).