2-17. Test Run Procedure
YES
NO
YES
YES
NO
NO
Fig. 2-14
Recheck the items to check before the test run. (See 2-18)
Check the combination (wiring) of indoor and outdoor units. (See 2-21-1)
Is system “single-type”?
Is outdoor unit multiple?
(See 2-21-2) How to Set the
Outdoor Unit System Address
Set the outdoor unit system address.
(See 2-21-1) How to Set
Automatic Address
Set the automatic address setting from
outside unit or remote controller.
(*) Indicate (mark) the combination number.
(See 2-21-3, 4)
Turn ON the indoor and outdoor power.
Automatic Address
Set the remote controller to “test run”.
(See 2-19)
Can operation be started?
Return the remote controller to normal control.
Turn ON the indoor
and outdoor power.
Automatic
Address
(See 2-20)
Refer to “Table of Self-Diagnostic
Functions” to check the system.
In addition, refer to Item 2-21 and
correct any items that need to
be corrected.
Note: Check the indoor-side drainage.
(*) Required for simultaneous-operation
multi systems and for group control.