1
1-181
For the shield part of the shielded cable, twist the end out, crimp it with a
round terminal, and connect it to the SG screw.
fter crimping it with a round terminal, wrap it with insulating tape so there
are no spaces and adjust it so the shield part does not touch any live parts.
Crimp the round terminal
Wrap it well with insulating
tape so there are no spaces.
Shield part
Model name Power supply
Maximum electric
current
1
Control cable
2
Ssc
U-100PE1E5 220/230/240V~ 25A
U-125PE1E5 220/230/240V~ 28A
U-140PE1E5 220/230/240V~ 30A
Caution
Be sure that the shield part of the shielded cable does
not touch the terminal block or any live parts.
Failure to do so may lead to electric shock or fire.
1 Use a shielded cable for the control cable. Overall extension less than 500m
Electrical work should be handled by Certificated Electrical work personnel by following “Technical standard of electric installation”
and “Regulated regulations of nation”.
Adjust wire size, length, earth leakage breaker, and fuse capacity according to each country’s Wiring regulations.
If capacity of power supply circuit and enforcement are not enough, it can causes the electric shock and a fire.
This equipment complies with EN/IEC 31000-3-12 provided that the short-circuit power Ssc is greater than or equals to 2 kVA at
the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment
to ensure; by consultation with the distribution network operator if necessary that the equipment is connected only to supply with a
short-circuit power Ssc greater than or equals to 2 kVA.
Ssc
SG
: Short circuit power
: Shows the earth for the shielded cable.
U-60PE1E5 220/230/240V~ 18A 0.75mm²
0.75mm²
0.75mm²
0.75mm²
0.75mm²
0.75mm²
0.75mm²
0.75mm²
0.75mm²
U-71PE1E5 220/230/240V~ 18A
U-71PE1E8 380/400/415V 3N~ 7A
U-100PE1E8 380/400/415V 3N~ 9A
U-125PE1E8 380/400/415V 3N~ 10A
3 Models U-71PE1E8, U-100PE1E8, U-125PE1E8 and U-140PE1E8 are intended for professional use.
Consult with the supply utility for permission of electrical connection.
U-140PE1E8 380/400/415V 3N~ 11A
3
3
4050kVA
4050kVA
3
3
6000kVA
6000kVA
6000kVA
Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conforms to CENELEC (HAR)
rating specifications) or use the cables based on IEC standard. (245 IEC57, 245 IEC66)
NOTE