28© Panasonic Industrial Devices SUNX Co., Ltd. 2016
Function Setting
3-3-3 Auxiliary Output Switching Function
*: When two or more SF4B / SF4B<V2> series are connected, cancel the protective function of all
SF4B / SF4B<V2> series.
<Setting of the auxiliary output>
Mode 0: Negative logic of the control output (OSSD 1 / 2) (factory setting)
Mode 1: Positive logic of the control output (OSSD 1 / 2)
Mode 2: ON during emission, OFF when emission is not done.
Mode 3: OFF during emission, ON when emission is not done.
Mode 4: OFF when the received light level is unstable (Note 1)
Mode 5: ON when the received light level is unstable (Note 1)
Mode 6: ON during muting
Mode 7: OFF during muting
Mode 8: ON in the light receiving condition
Mode 9: OFF in the light receiving condition
1RWHV7KLVFDQQRWEHXVHGZKHQWKH¿[HGEODQNLQJIXQFWLRQWKHÀRDWLQJEODQNLQJIXQFWLRQRUWKHPXWLQJVHWWLQJFKDQJLQJIXQF-
tion is used.
2) When using with SF4B / SF4B<V2> series only, if the external device monitor function is not used, set the monitor set-
ting to ineffective in “3-3-8 External Device Monitor Setting Changing Function.”
(Mode 9)
4. To Emission intensity
control function
Select output
(Mode 0)
(Mode 1)
(Mode 2)
Send
(Error)
To 3
OK
NG
࡮࡮࡮
Input pass-
word (*)
3. Auxiliary output
switching function
key operation
: FUNCTION
: ENTER
: CANCEL
: -
: +