Heating capacity in relation to supply water and outside temperature
Aquarea HT
Outside temperature Supply water temperature Models
30 35 40 45 50 55 60 65 9 kW (single phase)
WH-SHF09F3E5¹
WH-SHF09D3E5
(Phase-out models)
-15 9.0 9,0 8,9 8,8 8,5 8,5 8,0 7,8
-7 9,0 9,3 9,0 8,9 8,9 9,3 8,9 8,9
2 9,0 8,9 9,0 8,3 9,0 9,0 9,0 9,0
7 9,0 9,2 9,0 9,2 9,0 8,8 9,0 9,0
25 12,0 12,0 12,0 10,8 10,2 11,2 10,0 9,8
30 35 40 45 50 55 60 65 12 kW (single phase)
WH-SHF12F6E5¹
WH-SHF12D6E5
(Phase-out models)
-15 12,0 11,2 11,0 10,6 10,3 9,7 9,0 8,0
-7 12,0 11,9 11,5 11,2 10,8 10,2 9,9 9,6
2 12,0 11,5 11,5 10,5 11,0 10,8 10,7 10,3
7 12,0 11,6 12,0 11,5 12,0 11,7 12,0 12,0
25 12,0 12,0 12,0 12,0 12,0 12,0 12,0 12,0
30 35 40 45 50 55 60 65 9 kW (three phase)
WH-SHF09F3E8¹
WH-SHF09D3E8
(Phase-out models)
-15 9,0 9,0 8,9 8,8 8,5 8,5 8,0 7,8
-7 9,0 9,0 9,0 8,9 8,9 8,9 8,9 8,9
2 9,0 9,0 9,0 9,0 9,0 9,0 9,0 9,0
7 9,0 9,0 9,0 9,0 9,0 9,0 9,0 9,0
25 12,0 12,0 12,0 10,8 10,2 11,2 10,0 9,8
30 35 40 45 50 55 60 65 12 kW (three phase)
WH-SHF12F9E8¹
WH-SHF12D9E8
(Phase-out models)
-15 12,0 12,0 11,0 10,6 10,3 9,7 9,0 8,0
-7 12,0 12,0 11,5 11,2 10,8 10,1 9,9 9,6
2 12,0 12,0 11,5 11,3 11,0 10,8 10,7 10,3
7 12,0 12,0 12,0 12,0 12,0 12,0 12,0 12,0
25 12,0 12,0 12,0 12,0 12,0 12,0 12,0 12,0
Heating capacity [kW] of individual models of the bi-bloc system for different supply water and outside temperatures [°C].