Appendix
Cooling capacity in relation to supply water and and outside temperature
Aquarea LT
Aquarea LT
Cooling capacity in relation to supply water and and outside temperature
Outside temperature Supply water temperature Models
7 14 18 3 kW (single phase)
WH-SDC03E3E5
5 kW (single phase)
WH-MDC05F3E5
5 kW (single phase)
WH-SDC05E3E5
7 kW (single phase)
WH-SDC07C3E5
18 2.4 4.4 3.7
25 3.2 4.1 3.5
35 3.2 3.9 3.3
43 2.9 3.5 3.0
7 14 18
18 2.0 2.2 2.5
25 5.0 6.3 6.3
35 4.5 5.1 5.0
43 3.8 4.5 4.3
7 14 18
18 4.5 5.0 5.7
25 5.0 6.3 5.4
35 4.5 5.5 5.0
43 3.3 4.1 4.4
7 14 18
18 5.1
25 6.6
35 6.0 7.3 8.0
43 5.1
7 14 18 9 kW (single phase)
WH-SDC09C3E5
18 5.9
25 7.8
35 7.0 8.3 9.0
43 6.2
7 14 18 9 kW (single and three phase)
WH-MDC09
WH-SDC09C6E8
18 5.9
25 7.5
35 7.0 8.3 / 8.6 9.0 / 9.5
43 5.8
7 14 18 12 kW (single and three phase)
WH-MDC12 /
WH-SDC12
18 7.7
25 9.2
35 10.0 11.6 / 11.8 12.5 / 12.8
43 7.6
7 14 18 14 kW (single and three phase)
WH-MDC14 /
WH-SDC14
18 8.9
25 10.0
35 11.5 12.8 / 13.4 13.5 / 14.5
43 9.1
7 14 18 16 kW (single and three phase)
WH-MDC16 /
WH-SDC16
18 9.6
25 10.5
35 12.2 13.4 / 14.6 14.1 / 16.0
43 10.1
Cooling capacity [kW] of individual models of the split and monobloc systems for different outside temperatures