EasyManua.ls Logo

Panasonic WH-SXC09H3E8 - Page 106

Panasonic WH-SXC09H3E8
245 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
106
12.1.6.2 Target Zone 2 water temperature setting control
Start condition
- Heating zone 2 is ON by remote control or Timer or Auto Mode OR
- Cooling zone 2 is ON by remote control or Timer or Auto Mode.
Cancel condition
- Heating zone 2 is OFF by remote control or Timer or Auto mode AND
- Cooling zone 2 is OFF by remote control or Timer or Auto mode.
Target Zone 2 water temperature is calculated as below condition.
- Target Zone 2 water temperature = A (Base temperature) + B (shift temperature)
A (Base Temperature)
Compensation Direct
Value from the curve + User shift value set Direct value from user setting
* During heat mode and compensation select, if powerful mode is activated, higher value of WLo or WHi will be use
as curve value.
- B (shift temperature) value is depend on the room sensor selection at remote controller as below table:
B (Shift Temp.) B shift value is depend on the room sensor selection at remocon as table below
Sensor Selection
Water temperature B = 0
External Room Thermostat B = 0
Internal Room Thermostat
&
Room Thermistor
Cool Mode:
B = 0 ; when Zone OFF or Zone Room Thermo OFF
B = 1 * (room set temp. (R/C) – actual room temp.)
Max/Min Regulation of B: (Max: 5°C ; Min: -5°C)
Heat Mode:
B = 0 ; when Zone OFF or Zone Room Thermo OFF
B = follow Heating PI control contents
Pool Function Selected B = Delta value setting from remocon
*B = 0 regardless of which sensor selection, if SHP control bit is enable except Pool function select (maintain Pool “B”
value)
** Pool function also can be select at Zone 2 when optional PCB is connected and Zone 2 system is select.
Maximum/minimum regulation of Target Water Temperature.
Heating Cooling
Max
55°C (Below Ambient -15°C) *
60°C (Below Ambient -10°C) *
20°C
Min 20°C 5°C
* Between outdoor ambient -10°C and -15°C, max target decreases gradually from 60°C to 55°C.
Target Zone 2 Water Temperature (Heat mode only) during SG ready control
- If buffer tank selection is “NO” then following shift is carried out.
o While digital input is “10” or “11” then,
Final Target Zone 2 water temperature
= Target Zone 1 water temperature* (SG ready % setting (remote control menu))%
- If buffer tank selection is “YES”
o No shift of Target Zone 2 Water Temperature. Target Buffer Tank Temperature will change accordingly.
* Refer to “Buffer tank temperature control”

Table of Contents

Other manuals for Panasonic WH-SXC09H3E8

Related product manuals