EasyManua.ls Logo

Panasonic WH-SXC09H3E8

Panasonic WH-SXC09H3E8
245 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
126
12.13 Sterilization Mode
Purpose:
- To sterilize water tank by setting the required boiling temperature.
Remote control setting
- Days for sterilization function to start can be select.
- Time of selected day to start sterilization function.
- Boiling temperature (External heater is 55°C ~ 75°C, Internal heater is 55°C ~ 65°C)
- Maximum operation time is 5 minutes to 1 hour.
Start condition
- Tank connection set to “YES” by remote control
- Sterilization function selects “YES”.
- Sterilization signal received from remote controller by timer.
- Tank mode request ON.
Stop condition
- When boiling timer is completed. Boiling timer (Remote control set maximum operation time) start counting
once tank achieve boiling set temperature OR
- After 8 hours of operation since sterilization start.
- Tank mode request OFF.
Control content:
- During sterilization function activation time, target tank set temperature will internally change to boiling set
temperature.
- During sterilization activates, heat pump and heater (external or internal) will operate as normal tank mode to
achieve the boiling set temperature.
- Sterilization operation will end when stop condition is fulfill.
- After sterilization is complete, tank set temperature will resume to normal operation.
* Tank temperature may not achieve boiling set temperature if tank heater is select OFF OR external compressor
switch.

Table of Contents

Other manuals for Panasonic WH-SXC09H3E8

Related product manuals