Tank
30. Floor operation time (max)
Heat
Tank
31. Tank heat up time (max)
Heat
Tank
32. Tank re-heat temp.
-12°C ~ -2°C
33. Sterilization
②
①③
Initial setting: 8h
Set max operating hours of heating.
When max operation time is shortened, it can boil the tank more frequently.
It is a function for Heating + Tank operation.
30min ~ 10h
Initial setting: 60min
Set max boiling hours of tank.
When max boiling hours are shortened, it immediately returns to Heating
operation, but it may not fully boil the tank.
5min ~ 4h
Initial setting: -8°C
Set temp to perform reboil of tank water.
(When boiled by heat pump only, (51°C – Tank re-heat temp) shall become
max temp.)
Setting range is -12°C ~ -2°C
Initial setting: 65°C 10min
Set timer to perform sterilization.
1
2
3
Set operating day & time. (Weekly timer format)
Sterilization temp (55~75°C If use back-up heater, it is 65°C)
Operation time (Time to run sterilization when it reached setting temp
5min ~ 60min)
User shall set whether to use or not to use sterilization mode.