EasyManua.ls Logo

Panasonic WH-UD07JE5 - Installer Setup: System Configuration; PCB, Sensor, and Heater Settings

Panasonic WH-UD07JE5
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
3.4 WH-ADC0309J3E5UK WH-UD09JE5
Item Unit Outdoor Unit
Performance Test Condition
EN 14511
EN 14825
Cooling Capacity
Condition
(Ambient
/
Water)
A35W7
kW 7.60
BTU/h 25900
kcal/h 6540
Cooling EER
W/W 2.90
kcal/hW 2.50
Heating Capacity
Condition
(Ambient/Water)
A7W35 A2W35
kW 9.00 7.00
BTU/h 30700 23900
kcal/h 7740 6020
Heating COP
W/W 4.48 3.40
kcal/hW 3.85 2.92
Heating Erp
Low Temperature Application (W35)
Warmer Average Colder
Application Climate
Pdesign kW 7.0 7.0 7.0
Tbivalent/TOL °C 2 / 2 -10 / -10 -15 / -22
SCOP/ns (W/W)/% 5.75 / 227 4.90 / 193 4.18 / 164
Annual Consumption kWh 1627 2949 4132
Class A++ A++ A++
Medium Temperature Application (W55)
Warmer Average Colder
Application Climate
Pdesign kW 6.0 7.0 6.0
Tbivalent/TOL °C 2 / 2 -7 / -10 -15 / -22
SCOP/ns (W/W)/% 4.07 / 160 3.32 / 130 2.98 / 116
Annual Consumption kWh 1971 4354 4967
Class A++ A++ A+
DHW
Warmer Average Colder
Application Climate
COP/nwh (W/W)/% 3.50 / 140 3.00 / 120 2.47 / 99
AEC kWh 714 833 1013
Noise Level
Condition
(Ambient
/
Water)
A35W7 A7W35 A2W35
dB (A) Cooling: 50*** Heating: 51***
Power Level dB Cooling: 68***
Heating: 69***
Heating: 59****
Air Flow m
3
/min (ft
3
/min)
Cooling: 55.0 (1942)
Heating: 53.4 (1885)
Refrigeration Control Device Expansion Valve
Refrigeration Oil cm
3
FW50S (900)
Refrigerant kg (oz)
R32, 1.27 (44.8) (Pre-charged)
R32, 2.27 (80.1) (Maximum)
F-GAS
GWP 675
CO
2
eq (ton) (Precharged/Maximum) 0.857 / 1.532
Dimension
Height mm (inch) 795 (31-5/16)
Width mm (inch) 875 (34-15/32)
Depth mm (inch) 320 (12-5/8)
Net Weight kg (lbs) 61 (135)