94
Signal inputs
Optional
Thermostat
L N =AC230V, Heat, Cool=Thermostat heat,
Cool terminal
SG signal
Dry contact Vcc-Bit1, Vcc-Bit2 open/short
(System setup necessary)
Switching SW (Please connect to the 2 contacts
controller)
Heat/Cool SW
Dry contact Open=Heat, Short=Cool
(System setup necessary)
External
comp.SW
Dry contact Open=Comp.ON,
Short=Comp.OFF (System setup necessary)
Demand signal
DC 0~10V (System setup necessary)
Please connect to the DC 0~10V controller.
Outputs
Mixing valve
AC230V N=Neutral Open, Close=mixture
direction Operating time: 30s~120s
Pool pump AC230V
Solar pump AC230V
Zone pump AC230V
Thermistor inputs
Zone room sensor PAW-A2W-TSRT
Buffer tank sensor PAW-A2W-TSBU
Pool water sensor PAW-A2W-TSHC
Zone water sensor
PAW-A2W-TSHC
Solar sensor
PAW-A2W-TSSO
12.4.2.5 Recommended External Device
Specification
This section explains about the external devices
(optional) recommended by Panasonic. Please
always ensure to use the correct external device
during system installation.
For optional sensor.
1 Buffer tank sensor: PAW-A2W-TSBU
Use for measurement of the buffer tank
temperature.
Insert the sensor into the sensor pocket and
paste it on the buffer tank surface.
40
black
brown
blue
Ø
Dimensions (mm)
2 Zone water sensor: PAW-A2W-TSHC
Use to detect the water temperature of the
control zone.
Mount it on the water piping by using the
stainless steel metal strap and contact paste
(both are included).
93
70
35
Dimensions (mm)
3 Outdoor sensor: PAW-A2W-TSOD
If the installation location of the outdoor unit is
exposed to direct sunlight, the outdoor air
temperature sensor will be unable to measure
the actual outdoor ambient temperature
correctly.
In this case, optional outdoor temperature
sensor can be fixed at a suitable location to
more accurately measure ambient
temperature.
70
93
46
Dimensions (mm)
4 Room sensor: PAW-A2W- TSRT
Install the room temperature sensor to the
room which requires room temperature
control.
i
nsi
ns (
)
86
86
6030
5 Solar sensor: PAW-A2W-TSSO
Use for measurement of the solar panel
temperature.
Insert the sensor into the sensor pocket and
paste it on the solar panel surface.
40
black
brown
blue
Ø
Dimensions (mm)