4.4.2 Temperature control
PARAMETER CODE TYPE DEFAULT
Temperature control set point
SEt
D
--
Temperature control set point
CPt= On
SEt
D
20.0
Temperature control differential
(NOT visible with code “ CPt=
On”)
dIFI
D
4.0
4.4.3 Energy saving temperature control
PARAMETER CODE TYPE DEFAULT
energy saving enable
ESE
D
OFF
Set energy saving
SEt_ES
D
20
4.4.4 Compressor parameters
PARAMETER CODE TYPE DEFAULT
Minimum `On’ time.
dAS
F
2
Minimum time between two com-
pressor switch-ons.
dES
F
5
Compressor hour counter 1
AbCI
D
0
4.4.5 B1, B2, B3 sensor parameters
PARAMETER CODE TYPE DEFAULT
High temperature alarm (water)
HA1
D
60
Low temperature alarm (water)
LA1
U
-20
High temperature alarm (eva-
porator)
HA2
U
60
Low temperature alarm (eva-
porator)
LA2
U
3
High temperature alarm (am-
bient)
HA3
U
60
Low temperature alarm (am-
bient)
LA3
U
-20
4.4.6 Differential dinamic temperature parameter
PARAMETER CODE TYPE DEFAULT
Parameter
(5'
U
OFF
Differential
GW+$
U
5
Water minimum set
G0,Q
U
10
Water maximum set
'0$
U
25
4.5 Change parameters
4.5.1 Parameter (SEt / dIFI/ dEF )
Fig.2
set
set
set
set
set
PAr
esc
set
Y
Y
set
Y
P_nA tEr
CnP
r9E
Y
Y
PbI
Y
Y
Ar9
Y
HA1
Y
C1H
Y
Y
C1H2
SEt
Y
diFI
CF30 CF31
CF32
dEF
Y
Y
Y
Y
Y
4.5.2 Water temperature setting (see fi g.1/2)
1. Turn the main swicth (QS) to “ON” and wait for the “OFF” visualiza-
tion.
2. Press the buttons “
esc
” “
set
” together to enter on the parameter
type “D” .
3. Select the parameter “PAr”using “
”and “ ” buttons and
press the button “
set
” to enter.
4. Select the parameter “tEr”using “
”and “ ” buttons and
press the button “
set
” to enter.
5. Select the parameter “SEt”using “
”and “ ” buttons and
press the button “
set
” to enter.
6. Change the value using “
”and “ ” buttons and press the
button “
set
” to con rm and exit.
7. Press the button “
esc
” three times to exit.
4.5.3 Differential setting (see fi g.1/2)
1.Turn the main swicth (QS) to “ON” and wait for the “OFF” visualiza-
tion.
2.Press the buttons “
esc
” “
set
” together to enter on the parameter
type “D”
3.Select the parameter “PAr”using “
”and “ ” buttons and
press the button “
set
” to enter.
4. Select the parameter “tEr”using “
”and “ ” buttons and
press the button “
set
” to enter.
5. Select the parameter “dIFI”using “
”and “ ” buttons and
press the button “
set
” to enter.
6. Change the value using “
”and “ ” buttons and press the
button “
set
” to con rm and exit.
7. Press the button “
esc
” three times to exit.
4.5.4 Restore default parameters (see fi g.1/2)
1.Turn the main swicth (QS) to “ON” and wait for the “OFF” visualiza-
tion.
2.Press the buttons “
esc
” “
set
” together to enter on the parameter
type “D”
3.Select the parameter “PAr”using “
”and “ ” buttons and
press the button “
set
” to enter.
4. Select the parameter “P_nA”using “
”and “ ” buttons and
press the button “
set
” to enter.
5. Select the parameter “dEF”using “
”and “ ” buttons and
press the button “
set
” to enter.
6. Change the value “OFF” to “On” using “
”and “ ” buttons
and press the button “
set
” to con rm and exit.
7. Press the button “
esc
” three times to exit.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker Hiross Hyperchill Plus ICEP024 and is the answer not in the manual?

Parker Hiross Hyperchill Plus ICEP024 Specifications

General IconGeneral
BrandParker Hiross
ModelHyperchill Plus ICEP024
CategoryChiller
LanguageEnglish

Related product manuals