EasyManua.ls Logo

Parker Parflex - Parallel Medium Pressure System - Summation Method Example

Parker Parflex
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parker Hannifin Corporation
Parflex Division
Ravenna, Ohio
Bulletin No. 4660-PGP2T
26
Parflex
®
Flexible Gas Piping System
Design and Installation Guide
5. Sizing Section C – Section C must supply the water heater and dryer. The total appliance load is 34 +
25 = 59 CFH. Using the longest length method, the length is 78 ft. Referring to Table 17 under the 80 ft.
length column, we find that 3/4 inch black iron pipe has flow capacity above 59 CFH (118). Use 3/4 inch
black iron pipe to run Section C.
6. Sizing Section D – Section D is being run with CSST and will supply the water heater. The total load
is 34 CFH and the total length is 20 ft. + 30 ft. + 10 ft. + 18 ft. = 78 ft. Refer to Table 1 under the 80 ft.
column. We find that ½ inch (PGP-8) has capacity of 34 CFH (34). Use 1/2 inch (PGP-8) to run Section D.
7. Sizing Section E – Section E supplies the furnace/boiler. The total load is 75 CFH and the total length
is 10 ft. + 20 ft. = 30 ft. Referring to Table 1 under the 30 ft. column, we find that 3/4 inch (PGP-12) has
capacity above 75 CFH (96). Use 3/4 inch (PGP-12) to run Section E.
8. Sizing Section F – Section F supplies the range/oven. The total load is 50 CFH and the total length is 20
ft. + 30 ft. + 15 ft. = 65 ft. Referring to Table 1 under the 70 ft. column, we find that 1 inch (PGP-16 ) has
capacity above 75 CFH (157). Use 1 inch (PGP-16) to run Section E.
9.
Sizing Section G – Section G supplies the dryer. The total load is 25 CFH and the total length is 20 ft. +
30 ft. + 10 ft. + 12 ft. = 72 ft. Referring to Table 1 under the 80 ft. column, we find that ½ inch (PGP-8)
has capacity above 25 CFH (34). Use 1/2 inch (PGP-8) to run Section G.
Section 3.0 System Configuration & Sizing
3.2.6 Parflex System / Steel Pipe Hybrid System Example -
Continued
3.2.7 Summation of Pressure Drops Method - See example at www.parflexsystem.com
http://www.parker.com/parflexsystem/pdf_files/summation_example.pdf