Parflex
®
Flexible Gas Piping System
Design and Installation Guide
Shielding is not required at support points where the tubing is more than 3 inches away from any edge,
joist or plate and where unrestrained tubing has the freedom to move more than 3 inches away from a
possible point of penetration by a nail, screw or drill bit.
When multiple runs of tubing are located between two studs or joists, panel striker plates PSP (6"
x 17") can be used as an alternative to individual striker plates. Plates are commonly used near the
mounting side of manifolds and branch.
Section 4.0 Installation Practices
No Striker Plates Required
Panel Striker Plates Covering Branch Tees
in Rafter or Floor Joist Runs
Panel Striker Plates Covering Vertical
Tubing Runs Between STuds