Parker PV Series - 9.2 Basic adjustment LVDT; Table 4: setting dimensions LVDT core; Figure 16: Setting dimension A for LVDT armature; MAX-adjustment:

Parker PV Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
Parker Hannifin Manufacturing Germany GmbH & Co. KG
Pump & Motor Division Europe
Chemnitz, Germany
Electro hydraulic proportional controls version 45 for
axial piston pumps, PV series
Bulletin MSG30-3254-INST/UK
Installation and setup manual
9.2 Basic adjustment LVDT
The inductive position transducer for displace-
ment feedback (LVDT) and the compensator
valves are factory preset and the settings are
secured. New or readjustment is only neces-
sary after repair.
LVDT for displacement feedback:
Prior to a basic setting the adjustment of the
armature length is to be checked / readjusted
(see figure 16). The exact dimension for this
setting is given in table 4:
Size Size Serie 45
1 PV016-028 73.5
2 PV032-046 73.5
3 PV063-092 75.0
4 PV140-180 75.0
5 PV270 75.0
6 PV360 75.0
Table 4: setting dimensions LVDT core
Figure 16: Setting dimension A for LVDT armature
The adjustment is secured by a removable glue.
A new setting again has to be secured to avoid
uncontrolled re-setting.
At full upstroked pump the mechanical adjust-
ment can be verified: The voltage at the LVDT
output (pin 25 at the control module) should
have a value as given in the table below (± 0,2 V).
Zero adjustment:
Next the zero adjustment of the LVDT is to be
checked. The LVDT and the solenoid of the
displacement control valve are to be connected
according to chapter 9 to the electronic control
module.
Size voltage size voltage
PV016 6.34 V PV063 7.12 V
PV020 6.06 V PV080 6.48 V
PV023 5.87 V PV092 6.10 V
PV028 5.50 V PV140 5.24 V
PV032 6.40 V PV180 3.83 V
PV040 5.70 V PV270 4.06 V
PV046 5.43 V PV360 4.06 V
Protection plug
with o-seal
Zero adjustment
(sealed)
Do not touch!
electrical
connection
Figure 17: Iinductive positon transducer (LVDT),
outside view
At running pump the command for the displace-
ment is to be set to 0 and the pressure relief valve
of the circuit / test rig has to be set to a pressure
> 25 bar. All other connections / valves in the
hydraulic circuit are to be closed.
The pump then will down stroke to deadhead
at the minimum pump compensating pressure
(10 ± 2 bar). By setting the zero adjustment
potentiometer (see figure 17) at the LVDT the
diagnosis output of the control module is to
be set to 0 V, as the actual displacement is the
minimum displacement that can be controlled.
After adjustment the potentiometer must be
sealed again.
MAX-adjustment:
Next the command for the displacement is to
be increased, until the maximum displace-
ment of the pump is reached. That can either
be monitored by using the diagnosis output or
a flow meter at the pump outlet. The maximum
displacement is reached, if the displacement /
flow does not further increase, even when the
input command is still raised.