BURNER SETUP & BOILER OPERATION
Table 5.3: Riello Burner Specifications
Table 5.2: Carlin Burner Specifications
CARLIN BURNER SPECIFICATIONS
Boiler
Model No.
Firing
Rate
Burner
Model No.
Air
Shutter
Nozzle Size
Pump
Pressure
Start-up Settings
Air Band
Head Bar
Flue Baffle
Note
4
EC(T)-e-03-075 .75 EZ-1HP Blank 0.60 70° B DEL³ 150 psig 0.55 0.60 - 0.65
Flue
Baffles
Installed
4
EC(T)-e-03-100 1.00 EZ-1HP Blank
0.85 70° A DEL 150 psig 0.65 0.85 - 1.00
Boiler
Model No.
Burner
Model No.
Air
Shutter
Nozzle Size
Pump
Pressure
Start-up Settings
Head Dim. A Air Band
EC(T)-e-04-125 99FRD Blank 1.00 x 70° B DEL³ 150 psig 2 40% open
EC(T)-e-04-150 99FRD Blank
1.25 x 60° B DEL 150 psig 3 60% open
EC(T)-e-05-175 99FRD Open 1.50 x 60° B HAGO³ 150 psig 5 10% open
EC(T)-e-05-200 99FRD Open
1.65 x 60° B HAGO 150 psig 5 45% open
EC(T)-05-250 99FRD Open 2.00 x 60° B HAGO³ 150 psig 8 100% open
Not for use
with flue
baffles
4
EC(T)-06-275 102CRD Open 2.25 x 60° B DEL³ 150 psig 6 100% open
EC(T)-06-300 102CRD Open
2.50 x 60° B DEL 150 psig 8 100% open
Table 5.1: Beckett Burner Specifications
BECKETT BURNER SPECIFICATIONS (140 psig Pump Pressure)
Boiler
Model No.
Burner
Model No.
Burner Head Static Plate Nozzle Size
Start-up Settings
Head
Setting
Flue Baffle
Note
4
Air Shutter Air Band
EC(T)-e-03-075 AFG-L1¹ L1¹ 3-3/8” 0.65 60° B HAGO³ 9.0 2 N/A
Flue
Baffles
Installed
4
EC(T)-e-03-100 AFG-L1 L1 3-3/8”
0.85 60° B HAGO 10.0 1
N/A
EC(T)-e-04-125 AFG-F6 F6 2-3/4” 1.10 80° A DEL³ 5.0 1 N/A
EC(T)-e-04-150 AFG-F6 F6 2-3/4”
1.25 80° B HAGO 8.0 1
N/A
EC(T)-e-05-175 AFG-MV1 M-V1-3 1.50 60° B HAGO³ 10.0 3 3
EC(T)-e-05-200 AFG-MV1 M-V1-3
1.75 60° B HAGO 10.0 3 * 4 *
EC(T)-05-250 AFG-MV1 M-V1-5 2.00 45° B HAGO³ 10.0 5 5
Not for use
with flue
baffles
4
EC(T)-06-275 CF-375 L1-S 2.25 45° P HAGO³ 10.0 6 2
EC(T)-06-300 CF-375 L1-S
2.50 45° P HAGO 10.0 6 3
* Riello 40F5 burner is factory set for 03 section boiler. Replace nozzle and update settings when using on 04 section boiler.
** Riello 40F10 burner is factory set for 04 section boiler. Replace nozzle and update settings when using on 05 and 06 section boilers
Factory Installed Nozzles and Factory Start-up Settings (Packaged Boilers or Burner Cartons) are indicated in Boldface.
1 Requires Low Firing Rate Baffle.
2 Remove Static Plate for 1.20 GPH Rate.
3 Shipped Loose with Packaged Boiler or Burner Carton.
4 Flue baffles are for use with residential models only (residential models include “e” prefix).
RIELLO BURNER SPECIFICATIONS
Burner
Model No.
Boiler
Size
Boiler
Model No.
Firing
Rate
Burner
Model No.
Nozzle Size
Pump
Pressure
Start-up Settings
Flue Baffle
Note
4
Turbulator Air Damper
40F5*
03
EC(T)-e-03-075 .75 F5 0.60 60° B DEL³ 155 psig 0.5 2.1
Flue
Baffles
Installed
4
EC(T)-e-03-100 1.00 F5
0.85 60° W DEL 145 psig 2.0 2.6
04* EC(T)-e-04-125 1.25 F5 1.00 60° W DEL³ 155 psig 2.5 3.4
40F10**
04 EC(T)-e-04-150 1.50 F10
1.25 60° B DEL 145 psig 1.5 3.1
05**
EC(T)-e-05-175 1.75 F10 1.35 60° B DEL
3
165 psig 2.0 2.5
EC(T)-e-05-200 2.00 F10 1.50 60° B DEL
3
170 psig 2.5 2.8
EC(T)-05-250 2.50 F10 2.00 60° B DEL
3
155 psig 3.5 4.2
Not for use
with flue
baffles
4
06**
EC(T)-06-275 2.75 F10 2.25 60° B DEL
3
150 psig 4.0 4.2
EC(T)-06-300 3.00 F10 2.50 60° B DEL
3
145 psig 4.5 4.2
* Start-up Head Setting and Air Band Setting updated on EC(T)-e-05-200.