5.5.5. Default settings
The Table 4 shows the standard settings of the P18D transdu-
cer. The settings can be restored via the RS-485 interface after writing
the value „1” to the registry 4020.
Parameter
description
Para-
meter
address
Standard value
P18D-0XX,
P18D-3XX
P18D-1XX,
P18D-4XX
P18D-2XX,
P18D-5XX
Address 4001 1
Baud rate 4002 9600
Mode 4003 RTU 8N2
Averaging time 4005 30 [s]
X1 of the 1st
analog output
4007 0 -2000 -2000
Y1 of the 1st
analog output
4008 0 400 0
X2 of the 1st
analog output
4009 0 6000 6000
Y2 of the 1st
analog output
4010 0 2000 1000
X1 of the 2nd
analog output
4011 0 0 0
Y1 of the 2nd
analog output
4012 0 400 0
X2 of the 2nd
analog output
4013 0 10000 10000
Y2 of the 2nd
analog output
4014 0 2000 1000
Table 4