Insulation Tester
when the input terminals is Hi and Lo , The overload protective voltage is 600V. When the input terminals is V and
COM, the overload protective voltage is 1200 V under the voltage test; in other test mode ,the overload protective
voltage is 250V.
Batteries:eight AA batteries (NEDA 15A or IEC LR6) Meter use 1000 hours; Insulation test use: Meter can perform
at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into
1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
Insulation Measurement Range : 0.01 MΩ to 100.0 GΩ.
Insulation Test Voltages : 250, 500, 1000, 2500 V .
Insulation Source Voltage: + 20 %, - 0 %.
Insulation Short-Circuit Test Current : 3.0mA nominal.
Insulation Live Circuit Detection : Inhibit test if terminal voltage > 20 V prior to initialization of test.
Insulation Maximum Capacitive Load: Operable with up to 1 μF load.
Storage Temperature : -40 °C to 60 °C.
Operating Temperature: 0°C to 40 °C .
Storage Altitude: 12000m
Operating Altitude: 2000m 1000V CAT III,3000m 1000V Ⅱ
Temperature Coefficient: 0.05 × (specified accuracy) per °C for temperatures < 18 °C or > 28 °C.
Relative Humidity: 40%~75%(40%~60% when insulation test >1 GΩ)
Size: 180(L) mm×140(W) mm× 65(H)mm.
Weight: approx 900g.(not including battery)