USE AND MAINTENANCE MANUAL
Fans speed during
seasoning/preservation . The value of
this variable is amended based on the set-
up made during the last phase of a
performed program.
0 = High speed
1 = Low speed
(only if rin=1)
Refreshment period.
Interval between one refreshment and the
subsequent one. The refreshment is a
work pause in which cold, hot, humidifies
and dehumidifies are disabled.
0 ÷ 24 hours
(at 10 min steps)
0 = Disabled
Refreshment phase duration.
K7 Multifunction relay function choice.
0 = Refreshment
1 = Fans low speed
Signal delay and alarm display time of
minimum or maximum temperature or
humidity.
Minimum time between switch-off and
subsequent ignition of the compressor.
It also stops the fans if they are not active
for other functions
Dehumidification method selection
The separate dehumidification calls hot
and cold only for temperature
0 = cooling
1 = heating
2 = separate dehumidification
Dehumidification enabling
Ambient probe value correction
Humidity probe value correction
EnH = 1 hot enabled
EnH = 0 hot disabled
Hr = 1 enables humidity
management
Hr = 0 disables humidity
management The humidity
probe can be disconnected
without error on display.
The evaporator probe is
displayed instead of
humidity (if dE= 0)
Evaporator probe exclusion
0 = probe present
1 = probe absent
Type of defrosting, at cycle inversion (hot
gas) or resistance. The compressor output
is also activated with hot gas
1 = with hot gas
0 = with resistance
Minimum value attributable to setpoint
of temperature
Maximum value attributable to setpoint
of temperature
CHAP. 5 - Parameters programming