PLUS300 EXPERT U THR
Pag. 19
USE AND MAINTENANCE MANUAL
Temperature differential referred to Setpoint
for COLD BLOCK.
It constitutes the SET-btF limit below which the
cold call relay and the dehumidification relay
are disabled.
Temperature differential referred to
Setpoint for HOT BLOCK.
It constitutes the SET+btC limit above
which the hot call relay , the humidification
relay and the dehumidification relay are
disabled.
Limit time for DEHUMIDIFICATION.
If the dehumidification request is not
satisfied (achievement of humidity SET)
within the time (dEt), the variable (dEO) is
taken into consideration for the operation
to be performed. Counting starts at every
new dehumidification request.
(0 min ÷ 4 hours)
(1 min steps)
0 = Disabled
Operation to be performed in case Timeout
for dehumidification (dEt) intervenes
dEO = 0 an alarm signal (Ed) + buzzer +
alarm relay is given. The alarm is
displayed even when humidity set is
achieved; it does not block the normal
functioning and once silenced, the dEt
count re-starts.
dEO = 1 a refreshment of the duration (dr)
is launched and the timer relating to the
interval (Pr), if present, is recharged.
0 = alarm only
1 = a refreshment is
performed.
Net address for connection to TeleNET
supervision system.
Automatic cycles management or via
TeleNET. For managing the cycles via
TeleNET to set Aut=1
0 = local cycles
1 = TeleNET management
Seasoning or germination selection
0 = seasoning cycles active
1 = germination day/night
cycle active
Password: type of protection.
(Active when PA is different from 0).
0 = Total block. It is possible to
only see the temperature and
humidity set point.
1 = Blocks access in 1st and
2nd level programmes.
Blocks access in germination
cycle amendment and
programmes amendment.
2 = Blocks access in 1st and
2nd level programmes.
3 = Blocks access in 2nd level
programmes.
CHAP. 5 - Parameters programming