PV20a / PV30a pellet burner
page 33/ 41
DK9902A1 www.pelltech.eu
6 Status durations
HOLD FLAME
No signal from boiler thermostat (HOLD FLAME is ON or AUTO in
main menu).
END BURN
Maximum burning time (4 hours) is reached.
END BURN -> END
BLOW ->LEVEL
ERROR
After 8 rot of feeder pellets are continuously detected in feeders
inlet.
END BURN -> END
BLOW ->NO
PELLETS
Fuel level is not detected in feeders inlet in 4 min.
FLAME ERROR
Flame is not recognised more than 2 minutes.
HOLD FLAME
BURNING
Boiler’s thermostat has switcheds on.
END BURN
Max HOLD FLAME time (PAR12) is reached.
END BURN
END BLOW
End of burning. Feerder made 15
*
rot. + 10rot. Plus blow time
30sec. is reached.
BURNING
Boiler’s thermostate has switched on, feeder has made less than 8
rot and previous state was BURNING.
END BLOW
WAITING
No flame more than 1 min. and boiler thermostat is switched on.
STOPPED
No flame more than 1 min. and boiler thermostat is switched off.
LEVEL ERROR
No flame more than 1 min. Error from: BURN-> END BURN-> END
BLOW>LEVEL ERROR.
NO PELLETS
No flame more than 1 min. Error from: BURN-> END BURN-> END
BLOW->NO PELLETS.
NO POWER
WAITING
Main supply exists and boilers thermostat is swtiched on.
STOPPED
Main supply exists and boilers thermostat is swtiched off.
BURNING
If BURNING was before NO POWER and less than 15 min in NO
POWER.
Any other
WAITING
Boilers thermostat is switched on.