1020 Mono Filler
23
7 Program basics
This chapter describes a few basics of the Mono Filler program which can be used when starting
the program for the first time.
7.1 Out dosing
Dosing out of the weigher:
• Start the program with input 1 (start/stop)
• A pulse on input 3 (start dosing) starts the dosing
o Dosing starts and tare will be taken
o Output 1 (coarse) and output 2 (fine) turn on
o DAC is set to the coarse speed
• Turnover value is reached
o Output 1 (coarse) turns off
o DAC is set to fine speed
• Setpoint value is reached
o Output 2 (fine) turns off
o DAC is set to 0.00%
• Dosed weight within tolerance?
o Output 3 (ready) turns on
o Dosing is complete
• Dosed weight outside tolerance?
o Option to pulse input 2 (accept tolerance) to accept
o Output 3 (ready) turns on
o Dosing is complete
• A pulse on input 3 (start dosing) starts a new dosing
• Turn off input 1 (start/stop) to stop the program
7.2 In dosing with release valve
Dosing into the weigher and using a release valve:
Note the setting of the Weighing parameter:
• If set to Net, a tare will be taken before every dosing
• If set to Gross, tare will not be taken