Technical specication
Product type P216EEA-2K / P216EEA-101C
Power supply 208 - 240 VAC, 50/60 Hz
Pressure range
Adjustable 4 to 10 bar setpoint, prop band fixed at 2.0 bar
Adjustable 8 to 14 bar setpoint, prop band fixed at 2.5 bar
Adjustable 14 to 24 bar setpoint, prop band fixed at 4.0 bar
Adjustable 22 to 42 bar setpoint, prop band fixed at 5.0 bar
Pressure transducer P499VCS-405C pressure transducer included with 0- 50 bar range
Input signal 0 – 10 Vdc
Control action Direct or reverse mode
Maximum current 12 Amp
Minimum current 0,5 Amp
Protection class IP54
Ambient operating conditions -40 °C to 60 °C
Storage temperature -40 °C to 85 °C
Dimensions (H x W x D) 159 x 177 x 70 mm
Weight 1 kg
MTTR 20 years
Conformity
Johnson Controls International plc declares that these products are in compliance with the
essential requirements and other relevant provisions of the EMC Directive and
Low Voltage Directive.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult
the local Johnson Controls office. Johnson Controls Internation plc shall not be liable for damages resulting from misapplication or misuse of its products.
PB_P216_11 2016
www.johnsoncontrols.com
Building Efciency
Headquarters: Milwaukee, Wisconsin, USA