Installation Instructions
Issue Date September 2018
© 2018 Johnson Controls 1
Part No. 24-7664-1482, Rev. G
P66 Series Electronic Fan Speed Controls
Application
IMPORTANT: Use this P66 Series Electronic Fan
Speed Control only as an operating control. Where
failure or malfunction of the P66 control could lead to
personal injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the P66 control.
IMPORTANT: Utiliser ce P66 Series Electronic Fan
Speed Control uniquement en tant que dispositif de
contrôle de fonctionnement. Lorsqu'une défaillance
ou un dysfonctionnement du P66 control risque de
provoquer des blessures ou d'endommager
l'équipement contrôlé ou un autre équipement, la
conception du système de contrôle doit intégrer des
dispositifs de protection supplémentaires. Veiller
dans ce cas à intégrer de façon permanente d'autres
dispositifs, tels que des systèmes de supervision ou
d'alarme, ou des dispositifs de sécurité ou de
limitation, ayant une fonction d'avertissement ou de
protection en cas de défaillance ou de
dysfonctionnement du P66 control.
The P66 Series Electronic Fan Speed Controls are
pressure-actuated electronic motor-speed controllers
designed primarily to control condenser fan motors on
Heating, Ventilating, Air Conditioning, and
Refrigeration (HVAC/R) applications (Figure 1). These
controls vary the supply voltage to the fan motor in
response to the sensed refrigerant pressure, providing
direct response to changes in condenser pressure,
regardless of the variations in air delivery curves.
P66 controls are available with one or two pressure
sensor inputs. In dual sensor models, the control
selects the input with the greatest demand.
P66 control models are also available with NEMA 3R
(Rainproof) enclosures for outdoor applications
(Figure 1). These models come with a plastic
enclosure, appropriate gaskets, and low voltage wire
leads for 24 VAC power. In addition, the critical high
voltage components are encapsulated in a potting
compound.
Note: NEMA 1 models cannot be retrofitted in the
field to obtain the NEMA 3R (Rainproof) rating.
A P66 and speed controlled motor can replace On/Off
fan cycling controls, multiple speed motors, condenser
flood-back systems, temperature fan-speed controls,
and modulating louver systems.
Typical applications include:
computer room air conditioning
commercial air conditioning
commercial refrigeration
The P66 Series controls must be applied only to
single-phase motors intended for use with a solid-state
motor speed control. An applicable motor must be a
single-phase, permanent split-capacitor motor and
must be:
ball-bearing construction only (Sleeve-bearing
motors are not acceptable for use with P66
controls.)
designed to handle non-sinusoidal waveforms
generated by solid-state motor speed controls
designed to dissipate the motor heat generated at
reduced speed operation
!
CAUTION: Risk of Property Damage.
Use only single-phase Permanent Split-Capacitor
(PSC) motors approved by the manufacturer for
speed control applications with the P66 control.
Failure to use a single-phase PSC motor may
damage the motor and other property.
MISE EN GARDE: Risque De dégâts matériels.
Utiliser uniquement les moteurs PSC (Permanent
Split-Capacitor) monophasés approuvés par le
fabricant pour les applications de régulation de
vitesse avec le régulateur P66. L'utilisation d'un
moteur autre qu'un moteur PSC monophasé risque
d'endommager le moteur et de provoquer d'autres
dégâts matériels

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Penn P66AAB-1 and is the answer not in the manual?

Penn P66AAB-1 Specifications

Pressure Ratings IconPressure Ratings
control range (low pressure models)80 to 200 psig (552 to 1379 kPa)
control range (medium pressure models)140 to 350 psig (965 to 2413 kPa)
control range (high pressure models)300 to 500 psig (2048 to 3447 kPa)
effective throttling range (low pressure models)30 psi (207 kPa)
effective throttling range (medium pressure models)60 psi (414 kPa)
effective throttling range (high pressure models)90 psi (621 kPa)
maximum working pressure (low pressure models)200 psig (1379 kPa)
maximum working pressure (medium pressure models)350 psig (2413 kPa)
maximum working pressure (high pressure models)500 psig (3447 kPa)
maximum overpressure (low pressure models)250 psig (1724 kPa)
maximum overpressure (medium pressure models)400 psig (2758 kPa)
maximum overpressure (high pressure models)695 psig (4792 kPa)
Electrical Ratings IconElectrical Ratings
control voltage24 VAC, 1VA
line voltage range208 to 480 VAC
full load amperes (208 VAC)8.0
full load amperes (240 VAC)8.0
full load amperes (277 VAC)6.9
full load amperes (480 VAC)4.0
locked rotor amperes (208 VAC)16.5
locked rotor amperes (240 VAC)16.5
locked rotor amperes (277 VAC)14.3
locked rotor amperes (480 VAC)10.5
Operating Environment IconOperating Environment
maximum ambient temperature (208 VAC)130°F/54°C
maximum ambient temperature (240 VAC)130°F/54°C
maximum ambient temperature (277 VAC)130°F/54°C
maximum ambient temperature (480 VAC)150°F/66°C
minimum ambient storage temperature-40°F/-40°C (at all Voltages)
ambient storage temperature range-40°F/-40°C to 185°F/85°C