EasyManuals Logo

Penn P66AAB-1 User Manual

Penn P66AAB-1
9 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
P66 Series Electronic Fan Speed Controls Installation Instructions 5
Setup and Adjustments
The P66 control’s throttling range is fixed and cannot
be adjusted. The operating range pressure is
adjustable within the control pressure range. See the
Technical Specifications table for P66 model pressure
ratings.
To adjust the operating range pressure:
1. Apply a reliable pressure gauge to the controlled
system to monitor the pressure adjustments.
2. Access the operating range adjustment screw for
the P66 pressure transducer through the opening
in the upper left-hand corner of the P66 control
base (Figure 5).
Note: On dual pressure models, access to the
second adjustment screw is located in the lower right-
hand corner of the control base.
3. Turn the adjustment screw 1/2 turn (or less)
clockwise to increase the operating range
pressure or 1/2 turn (or less) counterclockwise to
decrease the operating range pressure.
Low Pressure Models (80 to 200 psig):
1/2 turn = approximately ± 9 psig (62 kPa)
Medium Pressure Models (140 to 350 psig):
1/2 turn = approximately ± 18 psig (124 kPa)
High Pressure Models (300 to 500 psig):
1/2 turn = approximately ± 35 psig (241 kPa)
IMPORTANT: Do not adjust the operating range
screw more than 1/2 turn before allowing the system
pressure to stabilize.
4. Check system pressure and repeat Step 3 until
the desired operating range pressure is attained.
!
CAUTION: Risk of Property Damage.
Limit any adjustments to two full turns in either
direction. Over-adjustment may prohibit modulation
of the motor resulting in high head pressures. All
pressure adjustments should be verified with the use
of refrigerant pressure gauges.
MISE EN GARDE: Risque de dégâts matériels.
Limiter tout réglage à deux tours complets dans
chaque sens. Un réglage excessif risque
d'empêcher la modulation du moteur, engendrant
des pressions de refoulement élevées. Tous les
réglages de pression doivent être vérifiés à l'aide
des manomètres de refrigerant.
Figure 5: Operating Range Adjustment Screw
Location
Checkout
Before leaving the installation, observe working
application for correct operation. See the Operation
section for a typical operational sequence.
Operation
Condensing unit installation, operation, and
maintenance determine the overall capability of
maintaining a satisfactory pressure by means of fan
speed control. Within the operating range, the P66
control provides air delivery in direct proportion to heat
rejection requirements. This allows the refrigeration
system to perform efficiently in very low ambient
temperatures.
The P66 pressure transducer provides direct response
to changes in condenser pressure, regardless of the
variations in fan delivery curves. The dual input
models select the pressure input from the transducer
sensing the highest pressure.
See Figure 6 for a typical operational sequence for a
P66 control.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Penn P66AAB-1 and is the answer not in the manual?

Penn P66AAB-1 Specifications

Pressure Ratings IconPressure Ratings
control range (low pressure models)80 to 200 psig (552 to 1379 kPa)
control range (medium pressure models)140 to 350 psig (965 to 2413 kPa)
control range (high pressure models)300 to 500 psig (2048 to 3447 kPa)
effective throttling range (low pressure models)30 psi (207 kPa)
effective throttling range (medium pressure models)60 psi (414 kPa)
effective throttling range (high pressure models)90 psi (621 kPa)
maximum working pressure (low pressure models)200 psig (1379 kPa)
maximum working pressure (medium pressure models)350 psig (2413 kPa)
maximum working pressure (high pressure models)500 psig (3447 kPa)
maximum overpressure (low pressure models)250 psig (1724 kPa)
maximum overpressure (medium pressure models)400 psig (2758 kPa)
maximum overpressure (high pressure models)695 psig (4792 kPa)
Electrical Ratings IconElectrical Ratings
control voltage24 VAC, 1VA
line voltage range208 to 480 VAC
full load amperes (208 VAC)8.0
full load amperes (240 VAC)8.0
full load amperes (277 VAC)6.9
full load amperes (480 VAC)4.0
locked rotor amperes (208 VAC)16.5
locked rotor amperes (240 VAC)16.5
locked rotor amperes (277 VAC)14.3
locked rotor amperes (480 VAC)10.5
Operating Environment IconOperating Environment
maximum ambient temperature (208 VAC)130°F/54°C
maximum ambient temperature (240 VAC)130°F/54°C
maximum ambient temperature (277 VAC)130°F/54°C
maximum ambient temperature (480 VAC)150°F/66°C
minimum ambient storage temperature-40°F/-40°C (at all Voltages)
ambient storage temperature range-40°F/-40°C to 185°F/85°C

Related product manuals