10 / 82
EN- Raychem920series-IM-H5687405/15
INDUSTRIAL HEAT TRACING SOLUTIONS
1.5.1 ENCLOSURE ASSEMBLY
Enclosure Assemblies
Description Catalog number Part number Weight/lbs
Raychem 920 controller–2 Pt in a 14" x 12" x 8" FRP
enclosure with window and quick-release latches,
control module, and operator console. 1P 30 A 277 V
SSR/pt. Controls two circuits, each with a 1-pole
solid-state relay. (Approved for Class 1, Div. 2 areas)
920*E4FWL*SIS302*SS3102*HTC*CON 10160-010 27
Raychem 920 controller–2 Pt in a 14" x 12" x 8" FRP
enclosure with window and quick-release latches,
control module, and operator console. Includes an
isolated 2-wire RS-485 communication option. 1P
30 A 277 V SSR/pt. Controls two circuits, each with
a 1-pole solid-state relay. (Approved for Class 1, Div.
2 areas)
920*E4FWL*SIS302*SS3102*HTC485*CON 10160-011 27
Raychem 920 controller–2 Pt in a 14" x 12" x 8" FRP
enclosure with window and quick-release latches,
control module, and operator console. 2P 30 A 277 V
SSR/pt. Controls two circuits, each with a 2-pole
solid-state relay. (Approved for Class 1, Div. 2 areas)
920*E4FWL*SIS302*SS3202*HTC*CON
10160-012 32
Raychem 920 controller–2 Pt in a 14" x 12" x 8" FRP
enclosure with window and quick-release latches,
control module, and operator console. Includes an
isolated 2-wire RS-485 communication option. 2P
30 A 277 V SSR/pt. Controls two circuits, each with
a 2-pole solid-state relay. (Approved for Class 1, Div.
2, areas)
920*E4FWL*SIS302*SS3202*HTC485*CON 10160-013 32
Raychem–Raychem Supervisory Software Raychem Supervisor 10391-002 1
IMPORTANT: The NEC (and CEC) rules specify that all ungrounded—i.e., hot—legs of a circuit, must be switched in the event of a
ground fault. This means for 207 V single-phase applications, you must specify a 2-pole (2P) version if you are not using external GFI
breakers.
Control Modules
Raychem 920 controller–Control module only
(No communications options installed)
920HTC 10260-001 1
Raychem 920 controller–Control module
with an isolated
2-wire RS-485 communication option installed
920HTC*485 10260-004 1
Raychem 920 controller–Control module
with modem
communications option installed
920HTC*MDM 10260-002 1
Operator Console
Raychem 920 controller–Operator console 920CON 10260-005 1
Contact your local representative for other available configurations that are not
listed above.