EN- Raychem920series-IM-H5687405/15
INDUSTRIAL HEAT TRACING SOLUTIONS
G.2 920 SERIES HTC CONFIGURATION SHEET V3.1X AND V3.2X
= Most commonly changed setting
IMPORTANT: Select temperature units before any other settings are entered.
Configuration Mode Main Menu
Parameter Factory User
Control Setpoint 68°F (20°C)
Lo TS 1 14°F (–10°C)
Lo Load 1.0 A
Hi GFI 50 mA
GFI Trip 75 mA
TS Alarms Configuration Sub-Menu
Parameter Factory User
TS 1 Fail Enable
Lo TS 1 Enable
Lo TS 1 14°F (–10°C)
Hi TS 1 Disable
Hi TS 1 *n/a (212°F (100°C))
TS 2 Fail Disable
Lo TS 2 Disable
Lo TS 2 *n/a (14°F (–10°C))
Hi TS 2 Disable
Hi TS 2 *n/a (212°F (100°C))
Lo TS Filter 0 min
Hi TS Filter *n/a (0 min)
LatchTSAlarms Yes
CTL TS Fail Enable
Other Alarms Configuration Sub-Menu
Parameter Factory User
Lo Load Enable
Lo Load 1.0 A
Lo Load Filter 0 sec
Hi Load Disable
Hi Load *n/a (30.0 A)
Hi Load Filter *n/a (0 sec)
Hi GFI Enable
Hi GFI 50 mA
Hi GFI Filter 0 sec