76 / 82
EN- Raychem920series-IM-H5687405/15
INDUSTRIAL HEAT TRACING SOLUTIONS
APPENDIX G FACTORY DEFAULT/CONFIGURATION SHEETS
G.1 CONFIGURATION SHEET V3.00
The following defines the default 920 Series control module configuration as set by Pentair
Thermal Managament for firmware V3.00. These settings are subject to change without notice. It
is the user’s responsibility to verify that all configuration parameters are chosen appropriately for
the intended application. IMPORTANT: It is recommended that all parameters common to both
Control Points A and B be programmed first.
Common Setup Sub-Menu
Parameter Factory User
Temp. Units °F
Firmware Version V3.0 n/a
Ext. Contact Input Not used
Ext. Contact Output Not used
FlashAlarmOutput Yes
Alarm Output State N.C.
Language English
PointBUsed Yes
Passcode 0
Communication Setup Sub-Menu
Parameter Factory User
HTCBUS Addr (factory ID)
Protocol HTCBUS
Baud Rate AUTO
Hardware None, modem,
RS-232 (if installed)
Driver Auto
Profile Auto
Tx Delay 0.02 secs
Point Setup Sub-Menu
Parameter Factory User
Tag TAG-32768
Switch Control Mode Proportional
Prop Band 4°F (2°C)
Deadband n/a
Switch Rating 30.0 A
Circuit Breaker 30.0 A
Max Power 7200 W
TS CTL Mode TS1-Fail Off
TS1 – High Limit Disable
TS2 – High Limit Disable
Volt Turns Ratio 1.00 to 1