EasyManua.ls Logo

Pentair 920 Series - Page 14

Pentair 920 Series
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14 / 82
EN- Raychem920series-IM-H5687405/15
INDUSTRIAL HEAT TRACING SOLUTIONS
Temperature Sensors Terminal No.
Point A – Shield 25
Point A TS 1 Source (WHT) 26
Point A TS 1 Sense (WHT) 27
Point A TS 1 Common (RED) 28
Point A – Shield 9
Point A TS 2 Source (WHT) 10
Point A TS 2 Sense (WHT) 11
Point A TS 2 Common (RED) 12
Point B – Shield 29
Point B TS 1 Source (WHT) 30
Point B TS 1 Sense (WHT) 31
Point B TS 1 Common (RED) 32
Point B – Shield 13
Point B TS 2 Source (WHT) 14
Point B TS 2 Sense (WHT) 15
Point B TS 2 Common (RED) 16
IMPORTANT: Some RTDs may be constructed with the Sense wire color-coded as Black.
2.7.2 ALARM RELAY CONNECTIONS
The alarm output relay is a programmable dry contact output. It may be programmed for N.O.,
N.C., steady or flashing operation, and is typically used to annunciate an alarm to an external
device such as a DCS, PLC, etc.
IMPORTANT: The alarm relay is intended to be used for switching low-voltage, low-current
signals.
Do not use this relay to directly switch line voltages.
Ensure that your application stays
within the ratings of the relay contacts as defined in Appendix A on page 61.
The alarm relay may also be used in conjunction with the +9 Vdc source to switch an external,
line-voltage relay to drive a local pilot light, etc. Refer to the wiring diagrams in Appendix C on
page 68 for example connection details.
Alarm and Control Signals Terminal No.
Alarm relay dry contact output 17
Alarm relay dry contact output 18
Ground 19
+9 Vdc nominal Out (100 mAmps maximum) 1
Common 2
Common 3
2.7.3 EXTERNAL INPUT/OUTPUT
These input and output terminals are used to implement the Override and Ambient Temperature
Control Mode features. Refer to Section 3 on page 18 for programming details, and Appendix C on
page 68 for example wiring diagrams.
Miscellaneous Signals Terminal No.
External input (+) 20
External input (-) 21
External output (+) 4
External output(-) 5
2.7.4 COMMUNICATION SIGNAL CONNECTIONS
The communications terminal assignments change based on the type of option installed. If present
in a control module, the type of communications interface will be identified by a label located next
to the module’s rating label.

Table of Contents