EasyManua.ls Logo

Pentair 920 Series - High Temperature Alarms and Filter Times

Pentair 920 Series
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31 / 82
EN- Raychem920series-IM-H5687405/15
INDUSTRIAL HEAT TRACING SOLUTIONS
• ThisalarmmustbeenabledanditssetpointmustbebelowtheCONTROLSETPOINT
temperature if fail-safe mode uses the temperature from TS 1.
3.7.3 HIGH TEMPERATURE SENSOR 1 ALARM
Purpose: If enabled, the HIGH TS 1 ALARM allows for alarming of high temperature conditions as
sensed by the first temperature sensor (TS 1).
Alarm Mask: ENABLE or DISABLE
Range: –76°F to 1058°F (–60°C to 570°CF)
Procedure: Adjust the HIGH TS 1 ALARM temperature setpoint to the desired value. Note that the
HIGH TS 1 ALARM must be enabled in order to adjust the HIGH TS 1 ALARM temperature setpoint
unless the TS 1 HIGH LIMIT CUTOUT feature is enabled.
IMPORTANT: This alarm should only be used for applications involving a product that is sensitive
to over temperature. General use may result in nuisance alarms due to the outflow of hot product
or steam. This may be a case where the alarm should be enabled and nonlatching temperature
alarming used. A high temperature condition resulting from a forced on failure of the heating
circuit should first be alarmed by the SWITCH FAILURE ALARM. See section 3.8.18 on page 40 for
more information.
3.7.4 TEMPERATURE SENSOR 2 FAILURE ALARM
Purpose: Enabling TS 2 FAILURE provides indication of an open or shorted failure of TS 2.
Alarm Mask: ENABLE or DISABLE
Procedure: Enable or disable alarming of a failed second temperature sensor (TS 2) as required.
IMPORTANT:
• Ifnosecondsensorisinstalled,disablethisalarm.Thisfailurealarmshouldbeenabledifa
second temperature sensor is connected to the TS 2 input.
• Thisalarmisalwayslatchedandmustberesetbytheuser.
3.7.5 LOW TEMPERATURE SENSOR 2 ALARM
Purpose: If enabled, the LOW TS 2 ALARM allows for alarming of low temperature conditions as
sensed by the second temperature sensor (TS 2).
Alarm Mask: ENABLE or DISABLE
Range: –76°F to 1058°F (–60°C to 570°C)
Procedure: Adjust LOW TS 2 ALARM temperature setpoint to the desired value. Note that the LOW
TS 2 ALARM must be enabled in order to adjust the LOW TS 2 ALARM temperature setpoint.
IMPORTANT:
• Ifnosecondsensorisinstalled,thisalarmshouldbedisabled.Thisalarmshouldbeenabled
and the setpoint should be appropriate for the heating application. Maintaining a minimum
5°C differential between low temperature alarming and the CONTROL SETPOINT temperature
minimizes nuisance alarming due to momentary dips in temperature. Another alternative to
this is to configure the controller for non-latching temperature alarms.
• ThisalarmmustbeenabledanditssetpointmustbebelowtheCONTROLSETPOINT
temperature if fail-safe mode uses the temperature from TS 2.
3.7.6 HIGH TEMPERATURE SENSOR 2 ALARM
Purpose: If enabled, the HIGH TS 2 ALARM allows for alarming of high temperature conditions as
sensed by the second temperature sensor (TS 2).
Alarm Mask: ENABLE or DISABLE
Range: –76°F to 1058°F (–60°C to 570°C)
Procedure: Adjust the HIGH TS 2 ALARM temperature setpoint to the desired value. Note that the
HIGH TS 2 ALARM must be enabled in order to adjust the HIGH TS 2 ALARM temperature setpoint
unless the TS 2 HIGH LIMIT CUTOUT feature is enabled.
IMPORTANT: If no second sensor is installed, disable this alarm. This alarm may be used for
applications where a product that is sensitive to over temperature is involved. General usage could
result in nuisance alarms due to the flow of hot product or steam out. This may be a case where
the alarm could be enabled and non-latching temperature alarming used. A high temperature

Table of Contents