reset. All load-shedding parameters (including fail-safe) are configured with default values. The
CONSOLE SETPOINT MAXIMUM and MINIMUM are also configured with default values.
Procedure: Enter the “Copy Configuration Sub-Menu” and select DEFAULTS TO A.
3.11.3 COPY DEFAULTS TO POINT B (V3.11 AND UP)
Purpose: Loads the point-specific Pentair Thermal Managament default configuration
parameters, as defined in Appendix G, for Point B. As well, all of Point B’s maintenance data are
reset. All load-shedding parameters (including fail safe) are configured with default values. The
CONSOLE SETPOINT MAXIMUM and MINIMUM are also configured with default values.
Procedure: Enter the “Copy Configuration Sub-Menu” and select DEFAULTS TO B.
3.11.4 COPY POINT A TO POINT B (V3.11 AND UP)
Purpose: Copies the point-specific configuration parameters of Point A to Point B. Point A’s
configuration parameters are not changed.
Procedure: Enter the “Copy Configuration Sub-Menu” and select A TO B.
IMPORTANT:
• ToensurethattheTAGsforbothpointsarenotthesame,PointA’sTAGiscopied,thelast
character incremented by one, and then written to Point B’s TAG.
• Noneofthecommunicationsaddressesorthemaintenancedatavaluesarecopied.
3.11.5 COPY POINT B TO POINT A (V3.11 AND UP)
Purpose: Copies the point-specific configuration parameters of Point B to Point A. Point B’s
configuration parameters are not changed.
Procedure: Enter the “Copy Configuration Sub-Menu” and select B TO A.
IMPORTANT:
• ToensurethattheTAGsforbothpointsarenotthesame,PointB’sTAGiscopied,thelast
character incremented by one, and then written to Point A’s TAG.
• Noneofthecommunicationsaddressesorthemaintenancedatavaluesarecopied.