User Guide 368 / 604-606
6 / 28 Ref. MKT-UG-007 / A - 14.10.2016
3.3. Description and components location
3.4. Bypassing
The system must be equipped with a bypass. If a problem occurs, turn the valves to bypass the system as shown in the picture
below.
4 . Programming
Note: After 5 seconds without keypad input, the unit returns to normal operation mode and display the time of day.
4.1. Basic programming
Note: has two different functions according to the controller used :
For 604 controllers : the function is the day interval setting.
For 606 controllers : the function is the volumetric capacity setting.
Time of day
Brine dosage
Time clock regeneration (604 only)
A Press until desired hour appears then release.
Range from 0 through 23 hours.
The elapsed minutes will reset to zero when the hours are changed.
A Press until desired brine dosage appears then release.
Range from 0.2 kg to 6.0 kg;
from 0.2 kg to 1.0 kg by increments of 0.05 kg;
from 1.0 kg to 3.0 kg by increments of 0.1 kg;
from 3.0 kg to 6.0 kg by increments of 0.5 kg.
A Press until desired interval appears then release.
Range from 0 through 30;
0 = Disabled;
0.3 = Regeneration every 8 hours : at 2, 10 and 18 hours;
0.5 = Regeneration every 12 hours : at 2 and 14 hours;
1 - 30 = Regeneration every X days (every 3 days in this example).
Injector screen
Refill flow controller
Camshaft indicator
Regen button
Display
Time button
Salt button
Flow indicator (606 only)
Delayed regen indicator
AC adapter connection
Meter cable
Outlet
Drain
Inlet
Brine
Regen setting button
Normal
operation
In Bypass
In InOut Out
A
A