INSTALLATION
For Discharge Connection:
Use pipe, tubing or reinforced hose to make discharge
connection. Material selected must have sufficient strength
for operating pressures.
Discharge pipe should be sized so that flow velocity is below
8 ft./sec.
Use ONLY non-slamming check valves to prevent hydraulic
shock (water hammer).
Use gate, ball, or butterfly valve for isolation. Valve should be
fully open during operation.
Maintain proper pipe size throughout discharge system, using
as few elbows and tees as possible to keep friction loss to a
minimum.
Install pressure gauge after reducer as shown to check
operating pressure or shut-off head.
RECOMMENDED
Discharge priming
valve.
Non-slam or spring loaded check
valve.
Support
piping as
required.
Isolation Valve
Isolation valve to permit
servicing of check valve or
pump.
This fitting may be used to
check shut-off head.
These two views show
discharge fittings typical
of pump with suction lift.
Expansion joint with tie rods where needed.
Align piping to
minimize flange
stress.
Use Concentric Reducer to
minimize friction losses.
This view shows
discharge fittings
typical of pump with
flooded suction.
Pressure Gauge
Discharge pipe diameter at lest one
nominal pipe six larger than discharge
opening size.