4
Teel Operating Instructions and Parts Manual
4RJ93, 4RJ94 and 4RJ95
Teel Pool Pump With Integral Trap
®
E
N
G
L
I
S
H
Electrical (Continued)
VOLTAGE
Voltage at motor must be not more
than 10% above or below motor
nameplate rated voltage or motor may
overheat, causing overload tripping
and reduced component life. If voltage
is less than 90% or more than 110% of
rated voltage when motor is running
at full load, consult power company.
GROUNDING/BONDING
Install, ground, bond, and wire motor
according to local or National Electrical
Code requirements.
Permanently ground motor. Use green
ground terminal provided under
motor canopy or access plate (See Fig.
2); use size and type wire required by
code. Connect motor ground terminal
to electrical service ground.
Bond motor to pool structure. Use a
solid copper conductor, size No. 8
AWG (8.4 sq.mm) or larger. Run wire
from external bonding lug (See Fig. 2)
to reinforcing rod or mesh.
Connect a No. 8 AWG (8.4 sq.mm) solid
copper bonding wire to the pressure
wire connector provided on the motor
housing and to all metal parts of the
swimming pool, spa, or hot tub and to
all electrical equipment, metal piping
or conduit within 5 feet (1.5 m) of the
inside walls of swimming pool, spa, or
hot tub.
WIRING
Pump must be permanently connected
to circuit. The Wiring Chart below
gives correct wire and circuit breaker
sizes for the pump alone. If other
lights or appliances are also on the
same circuit, be sure to add their amp
loads to pump amp load before
figuring wire and circuit breaker sizes
(If unsure how to do this or if this is
confusing, consult a licensed
electrician). Use the load circuit
breaker as the master on-off switch.
AWG WIRE SIZE
1 115/230/1 15.3/7.6 20/15 12/14 8/14 6/14 6/12 4/10
1
1
/
2
115/230/1 19.2/9.6 25/15 10/14 8/14 6/12 4/10 4/10
2 230/1 12.0 20 14 14 12 10 10
WIRING CHART – RECOMMENDED WIRE AND FUSE SIZES
Max. Load Branch Fuse* Distance in Feet from Motor to Supply
Motor HP Volts/Ph Amp Rating Amps† 0 - 100 101 - 200 201 - 300 301 - 400 401 - 500
(*) Fusetrons are recommended instead of fuses on all motor circuits
(†) At 115/230V
Figure 2 – Typical ground screw and
bonding lug locations.
Figure 3 – Wiring hook-up diagram