9 | Page
V4.1
Connecting Source Power
Table 17 – Input Wiring
Wire size recommendations based on 600 VAC copper wire, rated either 60°C or 75°C.
Assuming 104°F (40°C) ambient and no more than 3 current carrying conductors in
raceway or earth (directly buried). If phase converter will be in warmer environments,
consult NEC Handbook for temperature correction factor.
Input Wiring Recommendations
Min. Wire
Min. Wire
PTS003 10 AWG 14 AWG
8 AWG 10 AWG
PT007/PTE007/PTS007 4 AWG 6 AWG
PT010/PTE010 3 AWG 4 AWG
PTE015 1/0 AWG 1 AWG
PT020/PTE020 - 1/0 AWG
PT030 300 kcmil 4/0 AWG
PT040 - 350 kcmil
PT050 2 x 250 kcmil 2 x 3/0 AWG
2 x 300 kcmil 2 x 250 kcmil
2 x 500 kcmil 2 x 350 kcmil
PTE207 4 AWG 6 AWG
- 1/0 AWG
PTS405 10 AWG 14 AWG
PT407/PTE407/PTS407 10 AWG 10 AWG
PT415/PTE415 4 AWG 6 AWG
PT420/PTE420 4 AWG 4 AWG
1 AWG 3 AWG
PT440 - 1/0 AWG
- 2/0 AWG
350 kcmil 250 kcmil
PT4150
2 x 250 kcmil
2 x 3/0 AWG
PT4175
2 x 250 kcmil 2 x 3/0 AWG