9 | Page
V4.1
Connecting Source Power
Table 17Input Wiring
Wire size recommendations based on 600 VAC copper wire, rated either 60°C or 75°C.
Assuming 104°F (40°C) ambient and no more than 3 current carrying conductors in
raceway or earth (directly buried). If phase converter will be in warmer environments,
consult NEC Handbook for temperature correction factor.
Input Wiring Recommendations
Min. Wire
Gauge (60°C)
Min. Wire
Gauge (75°C)
PTS003 10 AWG 14 AWG
PTS005
8 AWG 10 AWG
PT007/PTE007/PTS007 4 AWG 6 AWG
PT010/PTE010 3 AWG 4 AWG
PTE015 1/0 AWG 1 AWG
PT020/PTE020 - 1/0 AWG
PT030 300 kcmil 4/0 AWG
PT040 - 350 kcmil
PT050 2 x 250 kcmil 2 x 3/0 AWG
PT060
2 x 300 kcmil 2 x 250 kcmil
PT075
2 x 500 kcmil 2 x 350 kcmil
PTE207 4 AWG 6 AWG
PTE210
3 AWG
4 AWG
PTE215
1/0 AWG
1 AWG
PTE220
- 1/0 AWG
PTS405 10 AWG 14 AWG
PT407/PTE407/PTS407 10 AWG 10 AWG
PT410/PTE410
8 AWG
8 AWG
PT415/PTE415 4 AWG 6 AWG
PT420/PTE420 4 AWG 4 AWG
PT430
1 AWG 3 AWG
PT440 - 1/0 AWG
PT450
- 2/0 AWG
PT460
250 kcmil
3/0 AWG
PT475
350 kcmil 250 kcmil
PT4100
2 x 250 kcmil
2 x 3/0 AWG
PT4150
2 x 250 kcmil
2 x 3/0 AWG
PT4175
2 x 250 kcmil 2 x 3/0 AWG