3 | Page
V4.1
SPECIFICATIONS
General Specifications
Table 1 – General Specifications
Output Voltage – Standard Models
Approx. equal to input voltage
Output Voltage – Voltage Doubling Models
Approx. 2 x input voltage
Operating Temperature – PT
-10°C (14°F) to 50°C (122°F)
Operating Temperature – PTE
-10°C (14°F) to 40°C (104°F)
Operating Temperature – PTS
-10°C (14°F) to 40°C (104°F)
-20°C (-4°F) to 60°C (140°F)
Efficiency – Standard Models
Efficiency – Voltage-Doubling Models
Short Circuit Withstand Rating
Electrical Specifications
Table 2 – 230 V PT Models and Ratings
Power
(HP)
Output
(kVA)
Max Steady
State Output
Current (AAC)
Voltage
Range
Max AC
Input
Current (A)
Standby
(W/BTU/hr)
Energy
Loss
PT007 7.5 10.8 26
187-260
45 70/239 479
PT010 10 14.9 36 62 74/252 661
PT020 20 26.6 64 111 80/273 1,180
PT030 30 39.4 95 165 175/597 1,752
PT040 40 54.0 130 225 190/648 2,395
PT050 50 68.5 165 286 235/802 3,043
PT060 60 78.9 190 329 260/887 3,500
PT075 75 99.7 240 416 300/1,024 4,427