Grounding
Properly ground the phase converter according to local electrical code.
Connect the ground lug to the branch circuit or service ground conductor.
Ground the phase converter with an adequately sized conductor according to
local electrical code.
Ground wire recommendations based on solid to semi-rigid stranded copper
wire.
Table 16 Ground Wire Specifications
Models
Recommended
Circuit Breaker (A)
Wire Range (AWG)
Min Max
PTS003 30 10 2
PTS005 40 10 2
PT007/PTE007/PTS007
60
10
2
PT010/PTE010 80 8 2
PTE015
125
6
2
PT020/PTE020
150
6
2
PT030 225 4 2
PT040 300 4 2
PT050 400 3 2/0
PT060
500
2
2/0
PT075
600
1
2/0
PTE207 60 8 2
PTE210
80
6
2
PTE215 125 6 2
PTE220 150 6 2
PTS405 30 10 2
PT407/PTE407/PTS407
30
10
2
PT410/PTE410
40
10
2
PT415/PTE415
60
10
2
PT420/PTE420
70 8 2
PT430 100 8 2
PT440
150
6
2
PT450
175
6
2
PT460
200
6
2
PT475 250 4 2
PT4100 400 3 2/0
PT4150
400
3
2/0
PT4175
500 3 2/0
See terminal markings for additional wire size and torque information.