31
䋼Condition
䋾
mbient tem
erature: 20/30㷄
Load: Unloaded
䋼Distribution dat
䋾
Temperature of the cycle in each area (SV=-70㷄䇮air temperature)
Unit:㷄
Maximum Minimum
Middle of
cycle
Differential Maximum Minimum
Middle of
cycle
Differential
㽲
-67.6 -75.4 -71.6 ±3.9 -67.2 -75.6 -71.4 ±4.2
㽳
-68.8 -75.5 -72.2 ±3.4 -68.4 -75.8 -72.1 ±3.7
㽴
-66.6 -75.5 -71.1 ±4.5 -66.0 -75.7 -70.9 ±4.9
㽵
-69.0 -75.3 -72.2 ±3.2 -68.7 -75.6 -72.2 ±3.5
㽶
-67.6
-72.1 -69.9 ±2.3 -67.3 -72.4 -69.9 ±2.6
㽷
-70.6 -74.1 -72.4 ±1.8 -70.6 -74.3 -72.5 ±1.9
㽸
-70.7 -74.0 -72.4 ±1.7 -70.7 -74.2 -72.5 ±1.8
㽹
-70.4 -73.9 -72.2 ±1.8 -70.4 -74.1 -72.3 ±1.8
㽺
-70.2 -73.6 -71.9 ±1.7 -70.3 -73.8 -72.1 ±1.8
㽻
-69.1
-72.1 -70.6 ±1.5 -69.2 -72.3 -70.8 ±1.6
㽼
-70.3 -73.4 -71.9 ±1.6 -70.4 -73.6 -72.0 ±1.6
㽽
-70.1 -73.2 -71.7 ±1.6 -70.2 -73.3 -71.8 ±1.6
㽾
-69.2 -71.9 -70.6 ±1.4 -69.3 -72.1 -70.7 ±1.4
㽿
-69.8 -72.6 -71.2 ±1.4 -69.9 -72.9 -71.4 ±1.5
㾀
-69.2 -71.9 -70.6 ±1.4 -69.3 -72.0 -70.7 ±1.4
Average - - -71.5 - - - -71.5 -
Unit:㷄
Maximum Minimum
Middle of
cycle
Differential Maximum Minimum
Middle of
cycle
Differential
㽲
-68.5 -75.6 -72.2 ±3.6 -68.2 -76.0 -72.3 ±3.9
㽳
-69.4 -75.8 -72.6 ±3.2 -69.2 -76.2 -72.7 ±3.5
㽴
-67.7 -75.8 -71.8 ±4.1 -67.1 -76.2 -71.7 ±4.6
㽵
-69.6 -75.6 -72.6 ±3.0 -69.4 -75.9 -72.7 ±3.3
㽶
-68.0
-72.4 -70.2 ±2.2 -68.1 -72.8 -70.5 ±2.4
㽷
-70.6 -74.5 -72.6 ±2.0 -70.9 -74.9 -72.9 ±2.0
㽸
-70.7 -74.4 -72.6 ±1.9 -71.0 -74.8 -72.9 ±1.9
㽹
-70.3 -74.3 -72.3 ±2.0 -70.6 -74.7 -72.7 ±2.1
㽺
-70.2 -74.0 -72.1 ±1.9 -70.6 -74.4 -72.5 ±1.9
㽻
-69.1
-72.4 -70.8 ±1.7 -69.5 -72.7 -71.1 ±1.6
㽼
-70.3 -73.9 -72.1 ±1.8 -70.7 -74.3 -72.5 ±1.8
㽽
-70.1 -73.6 -71.9 ±1.8 -70.6 -73.9 -72.3 ±1.7
㽾
-69.1 -72.4 -70.8 ±1.7 -69.5 -72.6 -71.1 ±1.6
㽿
-69.8 -73.1 -71.5 ±1.7 -70.2 -73.4 -71.8 ±1.6
㾀
-70.6 -72.1 -69.1 ±0.8 -69.5 -72.6 -71.1 ±1.6
Average - - -71.7 - - - -72.0 -
䋼
mount of power consumption䋾
mount of power consumption when driving at cycle
SV=-70㷄䋩
Uni
䋺kWh/da
50Hz 60Hz 50Hz 60Hz
115V - 4.06 - 4.26
220V - 3.82 - 4.30
230V 3.89 - 4.17 -
Note:This data does not represent a guarantee of product performance.
Ambient temperature 20㷄 Ambient temperature 30㷄
mbient temperature 20㷄
50Hz 60Hz
Note:This data does not represent a guarantee
of
roduct
erformance
mbient temperature 30㷄
50Hz 60Hz